ELECTRICAL POWER
(P-140) Location of major electrical power subsystem
equipment.
The electrical power subsystem provides electrical energy sources, power
generation and control, power conversion and conditioning, and power
distribution to the spacecraft throughout the mission. For checkout before
launch, dc electrical power is supplied by ground support equipment. The
electrical power subsystem furnishes drinking water to the astronauts as a
byproduct of its fuel cell powerplants, and includes the cryogenic gas storage
system.
Each of the three fuel cell powerplants (produced by United Aircraft Corp.'s
Pratt & Whitney Aircraft Division, Hartford, Conn.) consists of 31 cells
connected in series. Each cell consists of a hydrogen compartment, an oxygen
compartment, and two electrodes (conductors) -- one hydrogen and one oxygen. The
electrolyte (substance through which ions are conducted) is a mixture of
approximately 72 percent potassium hydroxide and approximately 28 percent water
and provides a constant conduction path between electrodes. The hydrogen
electrode is nickel and the oxygen electrode is nickel and nickel oxide.
The reactants (hydrogen and oxygen) are supplied to the cell under regulated
pressure (referenced to a nitrogen gas supply which also is used to pressurize
the powerplants). Chemical reaction produces electricity, water, and heat, with
the reactants being consumed in proportion to the electrical load. The
byproducts -- water and heat -- are used to maintain the drinking water supply
and to keep the electrolyte at the proper operating temperature. Excess heat is
rejected to space through the space radiators. The fuel cell powerplants are
located in Sector 4 of the service module.
Three silver oxide-zinc storage batteries supply power to the CM during entry
and after landing, provide power for sequence controllers, and supplement the
fuel cells during periods of peak power demand. These batteries are located in
the lower equipment bay of the CM. A battery charger located in the same bay
re-charges the batteries after each use and assures that they will be fully
charged before entry. These batteries are produced by Eagle Picher Co., Joplin,
Mo.
Two other silver oxide-zinc batteries, independent of and completely isolated
from the rest of the dc power system, are used to supply power for explosive
devices. These batteries are not recharged. They are produced by the Electric
Storage Battery Co., Raleigh, N.C.
The cryogenic (ultra low temperature) gas storage system produced by Beech
Aircraft Corp., Boulder, Colo.) supplies the hydrogen and oxygen used in the
fuel cell powerplants, as well as the oxygen used in the environmental control
subsystem. The system consists of storage tanks and associated valves, switches,
lines, and other plumbing. The hydrogen and oxygen are stored in a semi-gas,
semi-liquid state; by the time they reach the fuel cells, however, they have
warmed considerably and are in a gaseous state, The system is located in Sector
4 of the service module beneath the fuel cell powerplants.
Three solid-state inverters, located in the lower equipment bay of the CM,
supply the ac power for the spacecraft. These inverters are devices which
convert dc electrical power into ac. Both the fuel cell powerplants and
batteries, the two electrical power sources in the spacecraft, produce dc power.
The inverters operate from the two 28-volt dc main buses (connecting circuits)
to supply 115 120-volt, 400-cycle, 3-phase ac power to two ac buses. Normally
two inverters are used; however, one inverter can supply all primary ac
electrical power needed by the spacecraft. If one inverter fails, a crewman can
switch in the standby. Two inverters cannot be paralleled (hooked up together).
The inverters are produced by Westinghouse Electric's Aerospace Electrical
Division, Lima, Ohio.
(P-141) Fuel Cell Powerplant.
EQUIPMENT
Oxygen Tanks (Beech Aircraft Corp., Boulder, Colo.) -- Two spherical dewar-type
tanks made of Inconel (nickel-steel alloy) in Sector 4 of the service module
store oxygen for production of Power by fuel cells, for command module
pressurization, and for metabolic consumption. Outer diameter of each is 26.55
inches and wall thickness is 0.020 inch. Tanks with accessories are 36.39 inches
tall. Each tank has an inner vessel with a diameter of 25.06 inches and wall
thickness of 0.061 inch, Rupture pressure of the tanks is l530 pounds per square
inch. Insulation between the inner and outer shells is fiberglass, paper mating,
and aluminum foil. In addition, a pump maintains a vacuum between the inner and
outer vessels, Each tank weighs 79-1/2 pounds, has a volume of 4,73 cubic feet,
and a capacity of 320 pounds -- 210 pounds for fuel cells and 110 pounds for
environmental control. Each tank has a repressurization probe with two heaters
and two fans to keep the tank pressurized and a capacitive probe which measures
the amount of oxygen, A resistance element measures temperature.
Hydrogen Tanks (Beech) -- Two spherical dewar type titanium tanks located in
Sector 4 of the service module contain the hydrogen that powers the fuel cell.
Outer diameter of each is 31.80 inches and wall thickness is 0.033 inch. Each
tank is 31.9 inches tall and has an inner vessel 28.24 inches in diameter with a
wall thickness of 0.046 inch. Rupture pressure is 450 pounds per square inch.
Unlike the oxygen tank, which has insulation between the inner and outer shells,
the hydrogen tanks have a vapor-cooled shield suspended in a vacuum as a heat
barrier. Each tank weighs 69 pounds, has a volume of 6.75 cubic feet, and a
capacity of 28 pounds of usable fluid. Similar to the oxygen tanks, they contain
repressurization and capacitive probes, a pump to maintain the vacuum, and
temperature transducers.
Batteries (Eagle Picher Co., Joplin, Mo.) -- Three silver oxide-zinc storage
batteries are in the command module lower equipment bay. Each has 20 cells with
potassium hydroxide and water as an electrolyte. battery cases are plastic,
coated with fiberglass epoxy, and are vented overboard for outgassing. Each is
6-7/8 by 5-3/4 inches and weighs 28 pounds. The batteries are rated at 40 ampere
hours, providing a high power-to-weight ratio. Open circuit voltage is 37.2
volts. The battery characteristics are such that a minimum of 27 volts can be
maintained until the battery is depleted, The batteries have been shock-tested
to 80-g impact. The batteries provide all CM power during entry and after
landing. They also supplement fuel cells during major thrusting maneuvers and
provide power for. the sequence system and fuel cell and inverter control
circuits.
Battery Charger -- The constant-voltage, current limited charger is 4 by 6 by 6
inches and weighs 4.3 pounds. The current is limited to 2.8 amperes so as not to
overheat the batteries. It has an operating life of more than 1,000 hours. The
charger is located near the entry and postlanding batteries.
Pyrotechnic Batteries (Electric Storage Battery Co,, Raleigh, N.C.) -- Each of
the two silver oxide-zinc batteries in the lower equipment bay has 20 cells with
potassium hydroxide and water as an electrolyte. The cases are plastic. There is
a relief valve venting arrangement for outgassing. Each is 2-3/4 by 3 by 6-3/4
inches and is rated at 0.75 ampere hours with an open-circuit voltage of 37.2
volts and a 20-volt minimum underrated load. They power mild explosive devices
for CM-SM separation, parachute deployment and separation, Saturn third stage
separation, launch escape tower separation, and other functions.
Fuel Cell Powerplants (United Aircraft Corporation's Pratt K Whitney Aircraft
Division, Hartford, Conn.) -- Three fuel cell powerplants, each 44 inches high,
22 inches in diameter, and weighing 245 pounds, are located in Sector 4 of the
SM. They are mainly constructed of titanium, stainless steel, and nickel. They
are rated at 27 to 31 volts under normal loads. There are 31 separate cells in a
stack, each producing 1 volt, with potassium hydroxide and water as electrolyte.
Each cell consists of a hydrogen and an oxygen electrode, a hydrogen and an
oxygen gas compartment and the electrolyte. Each gas reacts independently to
produce a flow of electrons. The fuel cells are nonregenerative. They are
normally operated at 400 degrees F with limits of 385 and 500 degrees.
Water-glycol is used for temperature control. The fuel cells use hydrogen,
oxygen, and nitrogen under regulated pressure to produce power and, as a
by-product, water.
Inverters (Westinghouse Electric's Aerospace Electrical Division, Lima, Ohio) --
Three solid-state inverters are in the lower equipment bay. Each is contained in
an aluminum enclosure and coldplated with a water-glycol loop. The inverters
weigh 53 pounds each and are 14-3/4 by 15 by 5 inches. They produce 1250
volt-amperes each, They convert 28-volt dc to 115-volt ac, 3 phase, 400 Hertz.
They are designed to compensate for input and output voltage variations. Two of
the three inverters are in constant use. They provide alternating current for
fuel cell pumps, environmental control system glycol pumps, spacesuit
compressors, and other circuitry.
(P-142) Electrical power subsystem components in CM lower equipment bay.
(P-143) Command Module wire harness is first assembled on this mockup stand.
DETAILED DESCRIPTION
CRYOGENIC STORAGE
The cryogenic storage subsystem supplies oxygen and hydrogen to the fuel cell
powerplants and oxygen to the environmental control subsystem and for initial
pressurization of the lunar module. Each of the two tanks of hydrogen and oxygen
holds enough fluid to assure a safe return from the furthest point of the
mission. The cryogenic tanks are pressurized by internal heaters after filling
is complete.
Two parallel dc heaters in each tank supply heat necessary to maintain pressure.
Two parallel 3-phase ac circulating fans circulate the fluid over the heating
elements to maintain a uniform density and decrease the probability of thermal
stratification. Relief valves provide overpressure relief and check valves
provide tank isolation. A malfunctioning fuel cell powerplant can be isolated by
a shutoff valve. Filters extract particles from the flowing fluid to protect
components. Pressure transducers and temperature probes indicate the
thermodynamic state of the fluid and capacitive quantity probes indicate the
amount of fluid in the tanks.
(P-144) Cryogenic tank (Hydrogen).
The systems can be repressurized automatically or manually. The automatic mode
is designed to give a single-phase reactant flow into the fuel cell and feed
lines at design pressures. The heaters and fans are automatically controlled
through pressure and motor switches. As pressure decreases, the pressure switch
in each tank closes to energize the motor switch, closing contacts in the heater
and fan circuits. Both tanks have to decrease in pressure before heater and fan
circuits are energized. When either tank reaches the upper operating pressure
limit, its pressure switch opens, again energizing the motor switch and opening
the heater and fan circuits to both tanks. The oxygen tank circuits are
energized at 865 psia minimum and de-energized at 935 psia maximum, The hydrogen
circuits energize at 225 psia minimum and de-energize at 260 psia maximum.
When the systems reach the point where heater and fan cycling is at a minimum
(due to a reduced heat requirement), the heat leak of the tank is sufficient to
maintain proper pressures provided flow is within proper values. The minimum
heat requirement region for oxygen starts at approximately 40-percent quantity
in the tanks and ends at approximately 25-percent quantity. Between these tank
quantities, minimum heater and fan cycling will occur under normal usage. The
heat needed for pressurization at quantities below 25 percent starts to increase
until at the 5-percent level practically continuous heater and fan operation is
required. In the hydrogen system, the quantity levels for minimum heater and fan
cycling are between approximately 53 and 33 percent, with continuous operation
occurring at approximately 1 percent.
(P-145) Schematic of cryogenic storage system.
The oxygen system heaters and fans can sustain proper pressures for 30 minutes
at a total flow of 10.4 pounds per hour (5.2 pounds per hour per tank). The
hydrogen system heaters and fans can sustain proper pressures at a total flow of
1.02 pounds per hour (0.51 pound per hour per tank).
Manual repressurization supplies power directly to the heaters and fans through
the control switches. It can be used in case of automatic control failure,
heater failure, or fan failure.
Tank pressure and quantity are monitored on meters located on the main display
console. The caution and warning system will activate on alarm when oxygen
pressure in either tank exceeds 950 psia or falls below 800 psia or when the
hydrogen system pressure exceeds 270 psia or drops below 220 psia. Pressure,
quantity, and reactant temperature of each tank are telemetered to MSFN.
(P-146) Cryogenic tank pressure and quantity measurement devices.
Oxygen relief valves vent at a pressure between 983 and 1010 psig and reseat at
965 psig. Hydrogen relief valves vent at a pressure between 273 and 285 psig and
reseat at 268 psig. Relief opening of the relief valves will be prevented if
possible to minimize the probability of improper reseating, resulting in
eventual depletion of one tank.
Overpressurization may be prevented in two ways. The first is to disable the
heater and fan circuits when tank quantities reach approximately 55 percent,
allowing pressure in the tanks to decrease. This provides wider range for
eventual pressure increase during minimum-value operation. This method retains
the maximum amount of fluid for spacecraft use. The second method is to perform
an unscheduled fuel cell purge to deplete tank pressure.
The reactant tanks have vacuum-ion pumps which function as ion traps to maintain
the vacuum between the inner and outer shells.
BATTERIES
The five silver oxide-zinc storage batteries of the electrical power subsystem
are located in the lower equipment bay of the CM.
Three rechargeable entry and post-landing batteries (A, B, and C) power the CM
systems after CM-SM separation. Before separation, the batteries provide a
secondary source of power while the fuel cells are the primary source. They
supplement fuel cell power during peak load periods (velocity change maneuvers),
provide power during emergency operations (failure of two fuel cells), and
provide power for power subsystem control circuitry (relays, indicators, etc.)
and sequencer logic. They can also be used to power pyro circuits.
Each entry and post-landing battery consists of 20 silver oxide-zinc cells
connected in series. The cells are individually encased in plastic containers
which contain relief valves that open at 35 +/- 5 psig, venting during an
overpressure into the battery case. Each battery case is vented overboard
through a common manifold and the urine/water dump line. The vent line prevents
battery-generated gas from entering the crew compartment.
In the event a battery case fractures, the vent is closed. The battery manifold
pressure is monitored on the meter and when it approaches CM pressure the vent
valve is opened to prevent the gas going into the cabin. Battery manifold
pressure can be used as an indication of urine/waste water dump line plugging.
Each battery delivers a minimum of 40 ampere hours at a current output of 35 amps
for 15 minutes and a subsequent output of 2 amps, or at a current output of 25
amps for 30 minutes and a subsequent output of 2 amps. At Apollo mission loads,
each battery can provide 50 ampere-hours.
Open circuit voltage is 37.2 volts. Since sustained battery loads are extremely
light (2 to 3 watts), voltages very close to open circuit voltage will be
indicated on the spacecraft voltmeter, except when the main bus tie switches
have been activated to tie the battery output to the main dc buses. Normally
only batteries A and B will be connected to the main dc buses. Battery C is
isolated during the pre-launch period and provides a backup for main dc bus
power. The two-battery configuration provides more efficient use of fuel cell
power during peak power loads and decreases overall battery recharge time.
The two pyrotechnic batteries supply power to activate ordnance devices in the
spacecraft. The pyrotechnic batteries are isolated from the rest of the
electrical power system to prevent the highpower surges in the pyrotechnic
system from affecting it and to assure source power when required. These
batteries are not recharged in flight. The entry and post-landing batteries can
be used as redundant source of power for initiating pyro circuits if either pyro
battery fails.
(P-147) Pyrotechnic battery.
FUEL CELL POWERPLANTS
Each of the three Bacon-type fuel cell powerplants is individually coupled to a
heat rejection (radiator) system, the hydrogen and oxygen cryogenic storage
systems, a water storage system, and a power distribution system.
The powerplants generate dc power on demand through an exothermic chemical
reaction. A byproduct of this chemical reaction is water, which is fed to a
potable water storage tank in the CM where it is used for astronaut consumption
and for cooling purposes in the environmental control subsystem. The amount of
water produced is proportional to the ampere-hours.
Each powerplant consists of 31 single cells connected in series and enclosed in
a metal pressure jacket. The water separation, reactant control, and heat
transfer components are mounted in a compact accessory section attached directly
above the pressure jacket.
(P-148) Location of electrical power subsystem radiators.
Powerplant temperature is controlled by the primary (hydrogen) and secondary
(glycol) loops. The hydrogen pump, providing continuous circulation of hydrogen
in the primary loop, withdraws water vapor and heat from the stack of cells. The
primary bypass valve regulates flow through the hydrogen regenerator to impart
exhaust heat to the incoming hydrogen gas as required to maintain the proper
cell temperature. The exhaust gas flows to the condenser where waste heat is
transferred to the glycol, the resultant temperature decrease liquifying some of
the water vapor. The motor-driven centrifugal water separator extracts the
liquid and feeds it to the potable water tank in the CM. The temperature of the
hydrogen-water vapor exiting from the condenser is controlled by a bypass valve
which regulates flow through a secondary regenerator to a control condenser
exhaust within desired limits. The cool gas is then pumped back to the fuel cell
through the primary regenerator by a motor-driven vane pump, which also
compensates for pressure losses due to water extraction and cooling. Waste heat,
transferred to the glycol in the condenser, is transported to the radiators
located on the fairing between, the CM and SM, where it is radiated into space.
Radiator area is sized to reject the waste heat resulting from operation in the
normal power range. If an emergency arises in which an extremely low power level
is required, individual controls can bypass three of the eight radiator panels
for each powerplant. This area reduction improves the margin for radiator
freezing which could result from the lack of sufficient waste heat to maintain
adequate glycol temperature. This is not a normal procedure and is considered
irreversible due to freezing of the bypassed panels.
(P-149) Fuel cell module accessories.
Reactant valves provide the connection between the powerplants and the cryogenic
system. They are opened during pre-launch fuel cell startup and closed only
after a powerplant malfunction necessitating its isolation from the cryogenic
system. Before launch, a valve switch is operated to apply a holding voltage to
the open solenoid of the hydrogen and oxygen reactant valves of the three
powerplants. This voltage is required only during boost to prevent inadvertent
closure due to the effects of high vibration. The reactant valves cannot be
closed with this holding voltage applied. After earth orbit insertion, the
holding voltage is removed and three circuit breakers are opened to prevent
valve closure through inadvertent activation of the reactant valve switches.
Nitrogen is stored in each powerplant at 1500 psia and regulated to a pressure
of 53 psia. Output of the regulator pressurizes the electrolyte in each cell
through a diaphragm arrangement, the coolant loop through an accumulator, and is
coupled to the oxygen and hydrogen regulators as a reference pressure.
(P-150) Flow and control of electrical power subsystem radiators.
Cryogenic oxygen, supplied to the powerplants at 900 +/- 35 psia, absorbs heat
in the lines, absorbs additional heat in the fuel cell powerplant reactant
preheater, and reaches the oxygen regulator in a gaseous form at temperatures
above 0 degrees F. The differential oxygen regulator reduces pressure to 9.5
psia above the nitrogen reference, thus supplying it to the fuel cell stack at
62.5 psia. Within the porous oxygen electrodes, the oxygen reacts with the water
in the electrolyte and the electrons provided by the external circuit to produce
hydroxyl ions.
Cryogenic hydrogen, supplied to the powerplants at 245 (+15, -20) psia, is
heated in the same manner as the oxygen. The differential hydrogen regulator
deduces the pressure to 8.5 psia above the reference nitrogen, thus supplying it
in a gaseous form to the fuel cells at 61.5 psia. The hydrogen reacts in the
porous hydrogen electrodes with the hydroxyl ions in the electrolyte to produce
electrons, water vapor, and heat. The nickel electrodes act as a catalyst in the
reaction. The water vapor and heat are withdrawn by the circulation of hydrogen
gas in the primary loop and the electrons are supplied to the load.
(P-151) Construction of cell.
Each of the 31 cells comprising a powerplant contains electrolyte which on
initial fill consists of approximately 83 percent potassium hydroxide (KOH) and
17 percent water by weight. The powerplant is initially conditioned to increase
the water ratio, and during normal operation, water content will vary between 23
and 28 percent. At this ratio, the electrolyte has a critical temperature of 360
degrees F. Powerplant electrochemical reaction becomes effective at the critical
temperature. The powerplants are heated above the critical temperature by ground
support equipment. A load on the powerplant of approximately 563 watts is
required to maintain it above the normal minimum operating temperature of 385§F.
The automatic in-line heater circuit will maintain powerplant temperature in
this range with smaller loads applied.
Purging is a function of power demand and gas purity. Oxygen purging requires 2
minutes and hydrogen purging 80 seconds. The purge frequency is determined by
the mission power profile and gas purity as sampled after spacecraft tank fill.
A degradation purge can be performed if powerplant current output decreases
approximately 3 to 5 amps during sustained operation. The oxygen purge has more
effect during this type of purge, although it would be followed by a hydrogen
purge if recovery to normal were not realized. If the performance degradation
were due to powerplant electrolyte flooding, which would be indicated by
activation of the pH high indicator, purging would not be performed due to the
possibility of increasing the flooding.
(P-152) Cutaway view of cell.
The application and removal of fuel cell loads causes the terminal voltage to
decrease and increase, respectively. A decrease in terminal voltage, resulting
from an increased toad, is followed by a gradual increase in fuel cell skin
temperature which causes an increase in terminal voltage. Conversely, an
increase in terminal voltage, resulting from a decreased load, is followed by a
gradual decrease in fuel cell skin temperature which causes a decrease in
terminal voltage. This performance change with temperature is regulated by the
primary regenerator bypass valve and provides the capability of operating over
an increased power range within voltage regulation limits.
The range in which the terminal voltage is permitted to vary is determined by
the high and low voltage input design limits of the components being powered.
For most components the limits are 30 volts dc and 25 volts dc. To remain within
these design limits, the dc bus voltage must be maintained between 31.0 and 26.2
volts dc. Bus voltage is maintained within prescribed limits during high power
requirements by the use of entry and post-landing batteries.
(P-153) Schematic of fuel cell module.
(P-154) Electrochemical flow in fuel cell.
Spacecraft systems are powered up in one continuous sequence providing the main
bus voltage does not decrease below 26.2 volts. If bus voltage decreases to this
value the power-up sequence can be interrupted for the time required for fuel
cell temperatures to increase with the resultant voltage increase, or the
batteries can be connected to the main buses reducing the fuel cell load. In
most cases, powering up can be performed in one continuous sequence; however,
when starting from an extremely low spacecraft load, it is probable that
power-up interruption or batteries will be required. The greatest load increase
occurs while powering up for a velocity change maneuver.
Spacecraft systems are powered down in one continuous sequence providing the
main bus voltage does not increase above 31.0 volts. In powering down from
relatively high spacecraft load levels, the sequence may have to be interrupted
for the time required for fuel cell temperature, and thus bus voltage, to
decrease.
(P-155) Fuel cell module.
If a powerplant fails it is disconnected from the main dc buses and the in-line
heater circuit is deactivated. Before disconnecting a fuel cell, if a single
inverter is being used, the two remaining powerplants are connected to each main
dc bus to enhance load sharing since bus loads are unbalanced. If two inverters
are being used, each of the remaining powerplants is connected to a separate
main dc bus for bus isolation, since bus loads are relatively equal.
(P-156) Pratt and Whitney technicians assemble fuel cell powerplants at plant in Hartford, Conn.
INVERTERS
Each inverter is composed of an oscillator, an eight-stage digital countdown
section, a dc line filter, two silicon-controlled rectifiers, a magnetic
amplifier, a buck-boost amplifier, a demodulator, two dc filters, an eight-stage
power inversion section, a harmonic neutralization transformer, an ac output
filter, current sensing transformers, a Zener diode reference bridge, a
low-voltage control, and an overcurrent trip circuit. The inverter normally uses
a 6.4 kiloHertz square wave synchronizing signal from the central timing
equipment which maintains inverter output at 400 Hertz. if this external signal
is completely lost, the free running oscillator within the inverter will provide
pulses that will maintain inverter output within +/- 7 Hertz. The internal
oscillator is normally synchronized by the external pulse.
The 6.4 kiloHertz square wave provided by central timing equipment is applied
through the internal oscillator to the eight-stage digital countdown section.
The oscillator has two divider circuits which provide a 1600-pulse per second to
the magnetic amplifier.
The eight-stage digital countdown section produces eight 400-cycle square waves,
each mutually displaced one pulse-time from the preceding and following wave.
One pulse-time is 156 microseconds and represents 22.5 electrical degrees. The
eight square waves are applied to the eightstage power inversion section.
The eight-stage power inversion section, fed by a controlled voltage from the
buck-boost amplifier, amplifies the eight 400-Hertz, square waves produced by
the eight-stage digital countdown section. The amplified square waves, still
mutually displaced 22.5 electrical degrees, are next applied to the harmonic
neutralization transformer.
The harmonic neutralization section consists of 31 transformer windings on one
core. This section accepts the 400-Hertz square-wave output of the eight-stage
power inversion section and transforms it into a 3-phase, 400Hertz 115-volt
signal. The manner in which these transformers are wound on a single core
produces flux cancellation which eliminates all harmonics up to and including
the fifteenth of the fundamental frequency. The 22.5-degree displacement of the
square waves provides a means of electrically rotating the square wave excited
primary windings around the 3-phase, wye-connected secondary windings, thus
producing 3-phase 400 cycle sine wave output. This 115-volt signal is then
applied to the ac output filter.
The ac output filter eliminates the remaining higher harmonics. Since the lower
harmonics were eliminated by the harmonic neutralization transformer, the size
and weight of this output filter is reduced. Circuitry in this filter also
produces a rectified signal which is applied to the Zener diode reference bridge
for voltage regulation. The amplitude of this signal is a function of the
amplitude of ac output voltage. After filtering, the 3-phase, 115-volt ac
400-hertz sine wave is applied to the ac buses through individual phase
current-sensing transformers.
The current-sensing transformers produce a rectified signal, the amplitude of
which is a direct function of inverter output current magnitude. This dc signal
is applied to the Zener diode reference bridge to regulate inverter current
output; it is also paralleled to an overcurrent trip circuit.
The Zener diode reference bridge receives a rectified dc signal, representing
voltage output, from the circuitry in the ac output filter. A variance in
voltage output unbalances the bridge, providing an error signal of proper
polarity and magnitude to the buck-boost amplifier via the magnetic amplifier.
The buck-boost amplifier, through its bias voltage output, compensates for
voltage variations. When converter current output reaches 200 to 250 percent of
rated current, the rectified signal applied to the abridge from the current
sensing transformers is of sufficient magnitude to provide an error signal,
causing the buck-boost amplifier to operate in the same manner as during an
overvoltage condition. The bias output of the buck-boost amplifier, controlled
by the error signal, will be varied to correct for any variation in inverter
voltage or a beyond-tolerance increase in current output. When inverter current
output reaches 250 percent of rated current, the overcurrent trip circuit is
activated.
(P-157) Size of static inverter.
The overcurrent trip circuit monitors a rectified dc signal representing current
output When total inverter current output exceeds 250 percent of rated current,
this circuit will disconnect an converter in 15 +/- 5 seconds. If current output
of any single phase exceeds 300 percent of rated current, this circuit will
disconnect an inverter in 5+1 seconds.
The disconnect is provided through relays located in the motor switch circuits
that connect the inverters to the ac buses.
Dc power to the inverter is supplied from the main dc buses through the dc line
filter. The filter reduces the high-frequency ripple in the input, and the 25 to
30 volts dc is applied to the silicon controlled rectifiers.
The silicon-controlled rectifiers are alternately set by the 1600
pulses-per-second signal from the magnetic amplifier to produce a dc square wave
with an on-time of greater than 90 degrees from each rectifier. This is filtered
and supplied to the buck-boost amplifier where it is transformer coupled with
the amplified 1600 pulses-per-second output of the magnetic amplifier to develop
a filtered 35 volts dc which is used for amplification in the power inversion
stages.
The buck-boost amplifier also provides a variable bias voltage to the
eight-stage power inversion section. The amplitude of this bias voltage is
controlled by the amplitude and polarity of the feedback signal from the Zener
diode reference bridge which is referenced to output voltage and current. This
bias signal is varied by the error signal to regulate inverter voltage and
maintain current output within tolerance.
The demodulator circuit compensates for any low-frequency ripple in the dc input
to the inverter. The high-frequency ripple is attenuated by the input filters.
The demodulator senses the 35-volt dc output of the buck-boost amplifier and the
current it to the buck-boost amplifier. An input dc voltage drop or increase
will be reflected in a drop or increase in the 35-volt dc output of the
buck-boost amplifier, as well as a drop or increase in current input to the
buck-boost amplifier. A sensed decrease in the buck-boost amplifier voltage
output is compensated for by a demodulator output, coupled through the magnetic
amplifier to the silicon-controlled rectifiers. The demodulator output causes
the silicon-controlled rectifiers to conduct for a longer time, thus increasing
their filtered dc output. An increase in buck-boost amplifier voltage output
caused by an increase in dc output to the inverter is compensated for by a
demodulator output coupled through the magnetic amplifier to the
silicon-controlled rectifiers causing them to conduct for shorter periods, thus
producing a lower filtered dc output to the buck-boost amplifier. In this
manner, the 35-volt dc input to the power inversion section is maintained at a
relatively constant level irrespective of the fluctuations in dc input voltage.
(P-158) Entry and post-landing battery.
The low-voltage control circuit samples the input voltage to the inverter and
can terminate inverter operation. Since the buck-boost amplifier provides boost
action during a decrease in input voltage to the inverter, in an attempt to
maintain a constant 35 volts dc to the power inversion section and a regulated
115-volt inverter output, the high boost required during a low-voltage input
would tend to overheat the solid-state buck-boost amplifier. As a precautionary
measure, the low-voltage control will terminate inverter operation by
disconnecting operating voltage to the magnetic amplifier and the first power
inversion stage when input voltage decreases to between 16 and 19 volts dc.
A temperature sensor with a range of 32 degrees to 248 degrees F is installed in
each inverter and will illuminate a light in the caution and warning system at
an inverter overtemperature of 190 degrees F. Inverter temperature is
telemetered to the ground.
BATTERY CHARGER
A constant-voltage, solid-state battery charger is located in the CM lower
equipment bay. It is provided 25 to 30 volts from both main dc buses and 115
volts 400-cps 3-phase from either of the ac buses. All three phases of ac are
used to boost the 25 to 30-volt dc input and produce 40 volts dc for charging.
In addition, Phase A of the ac is used to apply power for the charger circuitry.
The logic network in the charger, which consists of a voltage differential
amplifier (comparator), Schmitt trigger, current-sensing resistor, and a voltage
amplifier, sets up the initial condition for operation. The first stage of the
comparator is on, with the second stage off, thus setting the Schmitt trigger
first stage to on with the second stage off. Maximum base drive is provided to
the current amplifier which turns on the switching transistor. With the
switching transistor on, current flows from the transformer rectifier through
the switching transistor, current sensing resistor, and switch choke to the
battery being charged. Current lags voltage due to switching choke action. As
current flow increases, the voltage drop across the sensing resistor increases,
and at a specific level sets the first stage of the comparator off and the
second stage on. The voltage amplifier is set off to reverse the Schmitt trigger
to first stage off and second stage on. This sets the current amplifier off,
which in turn sets the switching transistor off. This terminates power from the
source, causing the field in the choke to continue collapsing, discharging into
the battery, then through the switching diode and the current sensing resistor
to the opposite side of the choke. As the electromagnetic field in the choke
decreases, current through the sensing resistor decreases, reducing the voltage
drop across the resistor. At some point, the decrease in voltage drop across the
sensing resistor reverses the comparator circuit, setting up the initial
condition and completing one cycle of operation. The output load current, due to
the choke action, remains relatively constant except for the small variation
through the sensing resistor. This variation is required to set and reset the
switching transistor and Schmitt trigger through the action of the comparator.
Battery charger output is regulated by the sensing resistor until battery
voltage reaches approximately 36 volts. At this point, the biased voltage
control network is unbiased, and in conjunction with the sensing resistor
provides a signal for cycling the battery charger. As battery voltage increases,
the internal impedance of the battery increases, decreasing current flow from
the charger. At 39 volts minimum, the battery is considered fully charged and
current flow becomes negligible.
POWER DISTRIBUTION
Dc and ac power distribution is provided by two redundant buses in each system.
A single-point ground on the spacecraft structure is used to eliminate ground
loop effects. Sensing and control circuits are provided for monitoring and
protection of each system.
Dc power is distributed with a two-wire system and a series of interconnected
buses, switches, circuit breakers, and isolation diodes. The dc negative buses
are connected to the single-point ground. The buses consist of the following:
1. Two main dc buses (A and B), powered by the three fuel cell powerplants
and/or entry and post-landing Batteries A, B, and C.
2. Two battery buses (A and B), each powered by its respective entry and
post-landing battery. Battery C can power either or both buses if the Batteries
A or B fail.
3. Flight and post-landing bus, powered through both main dc buses and diodes,
or directly by the entry and post-landing batteries through dual diodes.
4. Flight bus, powered through both main dc buses and isolation diodes.
5. Nonessential bus, powered through either dc Main Bus A or B.
6. Battery relay bus, powered by two entry and post-landing batteries (A and B)
through the individual battery buses and isolation diodes.
7. Pyro buses, isolated from the main electrical power subsystem when powered by
the pyro batteries. Entry batteries can be connected to the A or B pyro system
in case of loss of a pyro battery.
8. SM jettison controllers, powered by the fuel cell powerplants and completely
isolated from the main electrical power subsystem until activated during CSM
separation.
Power from the fuel cell powerplants can be connected to the main dc buses
through six motor switches (part of overload/reverse current circuits in the SM)
which are controlled by switches in the CM. Fuel cell power can be connected to
either or both of the main dc buses. When an overload occurs, the
overload-reverse current circuits in the SM automatically disconnect the fuel
cell powerplants from the overloaded bus and provide visual displays for
isolation of the trouble. A reverse current condition will disconnect the
malfunctioning powerplant from the dc system. Dc undervoltage sensing circuits
are provided to indicate bus low-voltage conditions. If voltage drops below
26.25 volts dc, the applicable dc undervoltage light on the caution and warning
panel will illuminate. Since each bus is capable of handling all loads, an
undervoltage condition should not occur except in an isolated instance (if too
many electrical units are placed on the bus simultaneously or if a malfunction
exists in the subsystem). A voltmeter is provided to monitor voltage of each
main dc bus, the battery charger, and each of the five batteries. An ammeter
monitors current output of the powerplants, batteries, and battery charger.
During high power demand or emergencies, supplemental power to the main dc buses
can be supplied from batteries A and B via the battery buses and directly from
battery C. During entry, spacecraft power is provided by the three entry and
post-landing batteries which are connected to the main dc buses before CM-SM
separation.
The nonessential bus permits nonessential equipment to be shut off during a
shortage of power (two fuel cell powerplants out). The flight bus distributes
power to in-flight telecommunications equipment. The flight and post-landing bus
distributes power to some of the in-flight telecommunications equipment and
float bag No. 3 controls. The post-landing bus receives power from the fuel
cells or entry and post-landing batteries through the main dc buses. After
completion of reaction control subsystem purge during main chute descent, the
entry batteries supply power to the post-landing bus directly through individual
circuit breakers.
The battery relay bus provides dc power to the dc and ac sensing unit, the fuel
cell, inverter control circuits, and some of the indicators on the main display
console. The pyrotechnic batteries supply power to ordnance devices used during
the course of the mission. The three fuel cell powerplants supply power to the
SM jettison controllers for the SM separation maneuver.
(P-159) DC power distribution.
Ac power is distributed with a four-wire system via two redundant buses, 1 and
2. The ac neutral bus is connected to the single-point ground. Ac power is
provided by one or two of the solid-state 115/200-volt 400-cps 3-phase
inverters. Dc power is routed to the inverters through the main dc buses.
Inverter No. 1 is powered through dc Main Bus A, inverter No. 2 through dc Main
Bus B, and inverter No. 3 through either dc Main Bus A or B by switch selection.
Each of these circuits has a separate circuit breaker and a power control motor
switch. The three inverters are identical and are provided with overtemperature
circuitry. A light indicator in the caution and warning group illuminates at 190
degrees F to indicate overtemperature. Inverter output is routed through a
series of control motor switches to the ac buses. Six switches control motor
switches which operate contacts to connect or disconnect the inverters from the
ac buses. The motor switch circuits are designed to prevent connecting two
inverters to the same ac bus at the same time. Ac loads receive power from
either ac bus through bus selector switches. In some instances, a single phase
is used for operation of equipment and in others all three. Over or undervoltage and overload sensing circuits are provided for each bus. Inverters
are automatically disconnected during overvoltage or overload. Ac bus voltage
fail and overload lights in the caution and warning group indicate voltage or
overload malfunctions. Phase A voltage of each bus is telemetered to ground
stations.
(P-160) AC power distribution.